ORDERING CODE
EK-FI1-TP-I
DESCRIPTION
The EK-FI1-TP-I universal I/O module from the ÆVO Series allows you to control up to 16 groups of electrical devices, such as lights and valves, or up to 8 motorized drives, such as blinds and 3-way valves, independently and in any combination you like. for this purpose, the device has outputs equipped with potential-free bistable relay contacts that guarantee that the set control status is maintained even in the event of a power failure.
The device is equipped with buttons for manual control and LEDs for status indication; a button allows you to switch between automatic and manual operation. The device has an integrated KNX bus communication module and is designed for mounting on a 35 mm profile rail. Power is supplied via the KNX bus and no auxiliary power supply is required.
FUNCTIONS / CHARACTERISTICS
- Switching lights on and off
- Control of motorized drives
- Manual control via buttons on the front
- Status indication of outputs via LEDs
- Configuration as a normally open or normally closed switch
- Outputs and channels can be set via ETS as independent or with copy function from another output or channel
- Control of ON/OFF valves and three-way valves
- Up to 8 logic functions (AND, OR, XOR, etc.), object comparison and arithmetic
- Block and forcing function for each channel
- Timing: delay in switching on and off, stair light function with warning signal
- Integration into scenarios
- Energy and operating hours counter configurable via bus
- Meteo alarms
TECHNICAL DATA
Supply
- Power supply 21-30 Vdc via KNX bus
- Bus current draw at start-up: 54 mA @30 Vdc, 49 mA @21 Vdc
- Bus current draw in stand-by: 10 mA @30 Vdc, 13 mA @21 Vdc
- Bus current draw during relay movement: 32 mA @21-30 Vdc
Outputs
• Switching lights on and off
• Control of motorized drives
• Manual control via buttons on the front
• Status indication of outputs via LEDs
• Configuration as a normally open/closed switch
• Outputs and channels can be set via ETS as independent or with copy function from another output or channel
• Control of ON/OFF valves and three-way valves
• Up to 8 logic functions (AND, OR, XOR, etc.), object comparison and arithmetic
• Block and forcing function for each channel
• Timing: delay in switching on and off, stair light function with warning signal
• Integration into scenarios
• Energy and operating hours counter configurable via bus
• Automatic control of motorized drives for protection from direct sunlight and weather conditions (rain, wind, frost)
Inputs
• 16 independent digital inputs [DI] for potential-free contacts, for example, for connecting traditional switches or buttons for on/off control of appliances
• 8 inputs individually configurable as analog [AI] for measuring room temperature using a passive temperature probe (NTC 10 kΩ at 25°C) to be connected to the input with the option of sending the value to the bus and thermostat functionality
• 8 independent channels (2 coupled inputs), for example, for connecting double buttons to control dimmers or motorized drives
• on/off control of individual and group appliances
• detection of the status of signal contacts (from safety devices, alarms, etc.)
• scenario recall and storage
• sending values (temperature, brightness, etc.) to the bus
• lock function and shift register function
Environmental conditions
- Operating temperature: - 5 ... + 45°C
- Storage temperature: - 25 ... + 55°C
- Transport temperature: - 25 ... + 70°C
- Relative humidity: 95% not condensing)
Other characteristics
- Housing in plastic material
- Mounting on 35 mm rail (according to EN 60715)
- Protection degree IP20 (installed device)
- Overvoltage class III (according to EN 60664-1)
- Classification climatic 3K5 and mechanical 3M2 (according to EN 50491-2)
- Pollution degree 2 (according to IEC 60664-1)
- Mechanical lifetime (min. cycles): 3 000 000
- Electrical lifetime (min. cycles): 100000 @8A / 25000 @16 A (Vac)
- Dimensions (LxHxP): 143 x 90 x 63 mm
- Weight: 505 g
CONFIGURATION AND COMMISSIONING
A detailed description of the parameters can be found in the device's application manual. ETS5 or later versions are required for configuration and commissioning. Application program for ETS: APEKFI1TPI##.knxprod (## = version).